Flohe DC High current isolator / DC High current

load breaker

 

The FRGL (6 - 36 kA) has been included in the range for the task of bi-polar membrane chlorine electrolysis. It features a pre-contact for switching under load (up to 750 V DC).


EFRG isolator and FRGL load breaker combinations have been used by industries in many bipolar membrane chlorine electrolysis plants. A control unit with reverse locking is available upon request.

The FRG and FRGL isolators can be supplied for copper designs or aluminium designs. They can be securely supported just by the busbar package and do not require wall support.

Fastening brackets can be supplied on request.

 

Technical data                            FRG                                    FRGL

max. nominal current                  120 kA                                 36 kA
max. nominal voltage                  3000 V                                 3000 V
max. switching voltage                ./.                                        750 V
Peak short circuit current             10x nominal current 1 sec      10x nominal current 1 sec
Insulation resistance                    5.000 V DC                          5.000 V DC
max. ambient air temperature      60°C                                    60°C
max. operating temperature         max. ambient temp. + 40°C   max. ambient temp. + 40°